Cov txheej txheem

Laboratory DGA

Ntawm -line DGA Monitor

Lub sijhawm

Peb lub hlis twg rau txhua xyoo

Nruam (txhua 30 feeb - 24 teev)

Gas ntes

Tag nrho 7+ gases (H₂, CH₄, C₂H₆, C₂H₄, C₂H₂, CO, CO₂, O₂, N₂)

Feem ntau 5-9 gases (nws txawv ntawm tus qauv)

Qhov tseeb

Siab (lab GC: ± 1 ppm)

Nruab nrab (± 5-15% ntawm kev nyeem ntawv)

Trend rhiab heev

Txwv los ntawm kev ua piv txwv zaus

Zoo heev - captures load-induced hloov

Tus nqi peev

~ $ 50-100 rau ib qho qauv

$5,000–$30,000 ib saib

Tus nqi khiav haujlwm

$200–1,000/xyoo (lub hlis twg)

$500–2,000/xyoo (consumables, calibration)

Zoo tshaj rau

Cov nkoj me me (tsawg dua lossis sib npaug li 10 units); tsis yog - tseem ceeb

>100 MVA, EHV/UHV; chaw taws teeb; paub -fault

Qhov zoo tshaj plaws zoo - hybrid mus kom ze:

1. Nruab rau ntawm - kab saib nyob rau sab saum toj 10–20% feem ntau cov transformers tseem ceeb.

2. Siv peb lub hlis twg lab DGA ntawm tag nrho lwm cov units.

3. Hla- siv tau ntawm - kab saib nrog cov qauv kuaj txhua 6-12 lub hlis.

4. Yog tias pom muaj qhov ua txhaum loj, tam sim ntawd coj mus kuaj kuaj kom pom tseeb + tag nrho cov spectrum.