Kev paub

Yog tias purity poob rau 95% vim huab cua nkag mus, GIS puas tseem ua haujlwm?

Jun 30, 2026 Tso lus

Q: Yog tias purity poob rau 95% vim huab cua nkag mus, GIS puas tseem ua haujlwm?

A: Nws yuav nyob twj ywm, tab sis kev nyab xeeb margins (arc quenching thiab txias) yog txaus ntshai txo.

Risks ntawm Low Purity:

❶ Txo Arc Quenching: Cua yog 100x phem dua SF6 thaum nres arcs. CB yuav tsis cuam tshuam.

❷ Thaum tshav kub kub Dissipation: Cov pa paug hloov pauv roj ceev thiab muaj peev xwm ua kom txias, ua rau kub dhau.

Cov qauv (IEC 60480):

• Gas Tshiab: Ntau dua lossis sib npaug li 99.9%.

• Ua pa roj: yuav tsum> 97%. Hauv qab 95% yuav tsum tau reclamation.

 

Peb txhais li cas SO2 thiab HF qib?

Q: Analyzer qhia 5 ppm ntawm SO2. Qhov tshwm sim li qub lossis kev ua txhaum sab hauv?

A: SO2 yog "Smoke Alarm" rau sab hauv arcing. Txhais raws li nram no:

SO2 Level

Txhais lus

Kev ua

< 1 ppm

Kev ua haujlwm li qub.

Kev saib xyuas niaj hnub.

1-5 ppm

Me PD lossis hnyav hloov.

Txo lub sijhawm xeem.

5-10 ppm

Ib qho teeb meem loj tshwm sim.

Tshawb xyuas siv UHF / Acoustic PD.

>10 ppm

Kev puas tsuaj loj heev.

Kev tshuaj xyuas tam sim/purification.

Cov Lus Qhia Tshwj Xeeb: Yog tias ob qho tib si SO2 thiab HF siab, koj muaj ACTIVE tsis xws luag tsim cov kua qaub tam sim no.

Xa kev nug