Xov xwm

RBX-H Sweep Frequency Response Analyzer (FRA Test)

Mar 12, 2020 Tso lus

Transformer yog cov khoom siv tseem ceeb hauv kab sib kis. Yog li ntawd, kev nyab xeeb kev ua haujlwm ntawm transformer plays lub luag haujlwm tseem ceeb hauv daim phiaj kev nyab xeeb. Technical Engineers ntawm HUAYI Fais fab tshawb nrhiav qhov ua rau ntawm transformer winding deformation thiab qhov tshwm sim muaj kev phom sij los ntawm kev tshuaj xyuas qhov kev txhaum winding deformation ntawm cov transformers. Nws yog ib qho tseem ceeb rau tag nrho daim phiaj kev ruaj ntseg qhov kev ua haujlwm ib txwm muaj.

 

Peb Cov Kws Ua Haujlwm tau npaj siab tias thaum lub tshuab hloov pauv tau raug luv luv tam sim no lossis lwm yam cuam tshuam, qhov deformation yog raws li hauv qab no:

Lub deformation ntawm winding yog tshwm sim los ntawm sab nraud quab yuam xws li cuam tshuam, inclination thiab vibration thaum lub sij hawm thauj mus los, uas ua rau winding hloov chaw. Qhov no deformed winding muaj qhov loj me, tab sis tsuas yog qhov sib txawv txav mus rau qhov tseem ceeb hloov. Lub inductance ntawm winding, lub inter-cake capacitance yog tas li, thiab lub capacitance hloov. General capacitance raug txo. Nyob rau hauv qhov sib npaug Circuit Court, lub resonance ncov hloov mus rau lub siab zaus. Yog li piv nrog cov qub spectrums, txhua qhov taw tes resonance tseem muaj nyob rau hauv kev ntsuas spectrum, thiab tsis muaj kev hloov pauv tshwm sim, tab sis cov peaks hloov mus rau qhov siab zaus (mus rau sab xis).

 

Ib nrab deformation ntawm ncuav mog qab zib, ib co unfixed xov ncuav mog qab zib yog squeezed nyob rau hauv qhov kev txiav txim ntawm lub luv luv-circuit electromagnetic quab yuam, thiab lwm yam yog elongated, (txuas ncaj qha mus rau ob tug ncej ntawm lub hwj chim, thiab tsis muaj tam sim no nyob rau hauv cov khoom siv hluav taws xob) thiaj li hais tias lub capacitance. nruab nrab ntawm lub ncuav yog hloov. Lub deformation ua rau qee qhov inductances hauv qhov sib npaug ntawm qhov sib npaug kom loj dua thiab qee qhov ua me; lub capacitance ntawm ncuav qab zib uas nyob rau hauv parallel nrog lub inductance kuj hloov. Thaum ntsuas qhov spectrum, qee qhov resonance ncov txav mus rau qhov siab zaus, thiab qhov siab tshaj tus nqi txo; qee qhov taw tes resonance txav mus rau qhov tsawg zaus, thiab lub ncov taw tes nce. Lub deformation cheeb tsam thiab deformation degree ntawm cov ncuav qab zib yog txiav txim los ntawm kev hloov ntawm resonance ncov.

 

luv luv Circuit Court ntawm lem (txuas ncaj qha mus rau ob tug ncej ntawm lub hwj chim, thiab tsis muaj tam sim no nyob rau hauv cov khoom siv hluav taws xob), theoretically hais, tom qab lub winding tshwm sim luv luv Circuit Court ntawm lub lem, inductance tus nqi txo, lub spectrum nkhaus hloov ho, lub amplitude. nce, thiab qee qhov resonance point peaks ploj mus. Tab sis qhov no yog txoj kev xav, qhov tseeb nws yog qhov nyuaj kom tau txais nws. Thaum lub sijhawm ua haujlwm luv luv tshwm sim thaum lub sijhawm ua haujlwm, lub kauj yuav raug hlawv, cov roj hnyav yuav tawm mus, thiab lub siab nyem valve yuav pib. Lub sijhawm no, cov roj chromatography ntawm lub transformer (siab txawv) yuav tsis tsim nyog, thiab cov transformer yuav raug kuaj xyuas.

 

Lead txoj kev tshem tawm thiab deformation, vim tias cov hlau lead yog ntev heev, thaum nws tsis ruaj khov, kev hloov pauv deformation tshwm sim thaum lub sijhawm ua haujlwm. Thaum cov hlau lead raug tshem tawm, ob-chaw nres nkoj capacitance yuav hloov hauv qhov sib npaug. Thaum lub teeb liab ntawm qhov nkag ntawm lub teeb liab hloov chaw, tab sis cov hlau lead capacitance nyob rau tib lub sijhawm nrog rau lwm cov circuits, yog li nws cov chan 0 tsis cuam tshuam rau qhov nkhaus spectral. Txawm li cas los xij, qhov tso tawm cov hlau lead hloov pauv tshwm sim, qhov kev hloov pauv ntawm cov hlau lead capacitance yuav hloov pauv qhov zaus teb nkhaus, tshwj xeeb tshaj yog rau qhov ntau ntawm 300 kHz mus rau 1 MHz nkhaus. Yog li ntawd, hauv qhov kev sim tiag tiag, qhov chaw txhaj tshuaj yog qhov nruab nrab los tiv thaiv cov teebmeem saum toj no. Yog hais tias cov lead-rau-hauv av capacitance raug txo, lub amplitude nyob rau hauv lub zaus band nce, thiab vice versa. Yog tias cov txhuas-rau-hauv av capacitance loj dua, nws qhia tau hais tias cov hlau lead txav mus rau lub plhaub, thiab cov hlau lead-rau-hauv av capacitance yuav me dua, nws qhia tau hais tias cov hlau lead txav mus rau qhov winding.

 

Lub winding tau txais radial deformation, thaum lub winding raug rau lub radial quab yuam, puab winding tau cog lus rau sab hauv, ob txoj kab uas hla thiab inductance ua me me. Lub sijhawm no, qhov kev ncua deb ntawm sab hauv thiab sab nrauv windings yuav loj dua, thiab lub peev xwm ua me me, uas yuav ua rau lub resonance ncov point nyob rau hauv lub spectrum mus rau lub siab zaus, thiab amplitude nce.

 

Lub winding twists thiab deforms axially. Thaum lub coil qhov chaw ntawm transformers (siab variation) yog loj los yog ib co ntawm lawv yog displaced, nrog rau qhov kev txiav txim ntawm electromagnetic quab yuam, lub winding yog twisted rau hauv ib tug S duab axially. Lub sijhawm no, ib feem ntawm lub ncuav mog qab zib capacitance thiab av capacitance raug txo. Hauv kev ntsuas spectrum, qee qhov ntawm cov resonance peaks txav mus rau qhov siab zaus kev taw qhia, thiab qhov amplitude ntawm resonance ncov txo qis hauv qhov tsawg zaus, lub ncov ntawm qhov nruab nrab zaus nce me ntsis, thiab qhov ntau zaus tsis hloov.

 

Raws li kev ntsuas ntawm cov yam ntxwv ntawm lub tshuab hluav taws xob sab hauv winding, Huayi Fais Fab tsim RBX-H transformer winding deformation tester, thiab siv qhov kev ua txhaum hauv qhov kev ntsuam xyuas cov lus teb (FRA) txoj kev uas tau tshawb xyuas los ntawm cov teb chaws tsim, nws tuaj yeem txiav txim siab ntawm qhov txhaum sab hauv. ntawm lub transformer. Cov cuab yeej yog txhawm rau txheeb xyuas qhov kev hloov pauv 'internal winding tsis muaj qhov sib txawv ntawm cov lus teb hloov pauv, thiab txiav txim siab lub tshuab hluav taws xob sab hauv ntawm lub tshuab hluav taws xob raws li qhov loj ntawm qhov sib txawv, qhov amplitude ntawm cov lus teb zaus, kev hloov ntawm cheeb tsam thiab cov lus teb zaus hloov. , raws li kev ntsuas qhov tshwm sim, nws tuaj yeem txiav txim siab tias seb lub tshuab hloov pauv puas loj thiab puas yuav tsum tau kho. Rau lub transformer khiav, tsis hais seb qhov zaus ntawm cov yam ntxwv daim ntawv qhia tau txais kev cawmdim ua ntej, qhov degree ntawm kev txhaum yuav raug txiav txim los ntawm kev sib piv qhov txawv ntawm cov yam ntxwv daim ntawv qhia ntawm lub coils ntawm faulty transformers. Tau kawg, yog tias daim ntawv qhia tus yam ntxwv winding ntawm transformer tau txais kev cawmdim, nws yooj yim dua los muab lub hauv paus tseeb dua rau kev ua haujlwm, kev soj ntsuam tom qab kev sib tsoo thiab kev saib xyuas ntawm transformers.

Nta ntawm Huayi fais fab transformer winding deformation tester

 

Lub zog kho vajtse siv DDS digital high-speed sweep-frequency txheej txheem los kuaj xyuas qhov tsis raug, xws li twisting, bulging, hloov chaw, tilting, tig-rau-tig luv-circuit deformation thiab theem-rau-theem tiv tauj luv-circuit.

Kev tswj xyuas tau siv cov microprocessor sib xyaw ua ke, xaiv cov khoom siv nrog qhov tseeb thiab kev ruaj khov, kev kub ceev dual-channel 16-ntsis A / D sampling (teb kev sim hloov pauv hloov pauv, waveform nkhaus hloov pom tseeb), rov kuaj dua rau tib theem, qhov rov ua dua ntawm kev ntsuas yog siab dua 99.5 feem pua.

 

Cov cuab yeej muaj ob qhov ntsuas qhov ntsuas, qhov ntsuas qhov ntsuas qhov ntsuas qhov ntsuas thiab qhov ntsuas qhov ntsuas qhov ntsuas qhov ntsuas, uas yog sib xws nrog ob hom kev ntsuas ntsuas hauv tsev tam sim no.

Tsuas yog lub tsheb sib txuas ntawm lub tshuab hloov pauv yuav tsum tau muab tshem tawm hauv cov txheej txheem kev sim, thiab txhua qhov kev sim ua tiav yam tsis tau nqa lub hau thiab disassembling lub transformer.

 

Thaum ntsuas qhov hloov pauv, cov neeg ua haujlwm xaim hluav taws xob tuaj yeem teeb tsa cov cim rau kev tawm tswv yim thiab tso tawm, uas tsis cuam tshuam rau kev ntsuas ntsuas. Cov neeg ua haujlwm xaim tuaj yeem nyob ntawm lub tank transformer kom muaj kev so, thiaj li txo qis kev siv zog.

Cov yam ntxwv amplitude-frequency ua raws li lub teb chaws kev ntsuas ntsuas ntawm amplitude-frequency yam ntxwv tester. Lub abscissa (frequency) yog tsim los ntawm linear indexing thiab logarithmic indexing. Yog li ntawd, cov ntawv luam tawm tuaj yeem yog linear indexing nkhaus lossis logarithmic indexing nkhaus, thiab cov neeg siv tuaj yeem xaiv raws li lawv xav tau.

 

Qhov ntsuas yog qhov ntse heev, thiab qhov ntsuas ntawm cov teeb liab tso zis amplitude tau hloov kho los ntawm software. Qhov siab tshaj plaws amplitude yog ± 10V, thiab cov qauv zaus raug hloov kho.

Lub ntsuas hluav taws xob muaj lub luag haujlwm los ntsuas ntau yam kab cheb- zaus tshuab, linear sweep ntsuas ntsuas zaus mus txog 2MHz, zaus ntsuas lub sijhawm yog 0.25kHz, 0.5kHz thiab 1kHz, yog li muab kev tshuaj xyuas ntxiv rau transformer deformation.

 

Muab cov keeb kwm nkhaus sib piv, thiab thauj khoom ntau qhov kev soj ntsuam ntawm keeb kwm nkhaus tib lub sijhawm, nws tuaj yeem xaiv cov nkhaus nkhaus thiab ua kab rov tav thiab ntsug. Nruab nrog cov kws tshaj lij kev tshuaj ntsuam xyuas thiab kev kuaj mob, nws tuaj yeem kuaj xyuas lub xeev ntawm transformer winding, thauj 6 nkhaus tib lub sijhawm, cia li xam qhov cuam tshuam ntawm txhua qhov nkhaus, tuaj yeem kuaj xyuas qhov deformation ntawm winding, thiab muab cov lus xaus ntawm kuaj mob.

 

Lub software tswj kev ua haujlwm muaj zog heev. Cov khoom tsim engineers ntawm Huayi Fais fab xav txog cov kev xav tau ntawm kev pab cuam, lub software cia li txuag ib puag ncig tsis zoo los muab lub hauv paus rau transformer winding deformation kuaj. Cov ntaub ntawv ntsuas tau raug txheeb xyuas thiab khaws cia, cov ntaub ntawv hluav taws xob (Lord) tau txais kev cawmdim, thiab cov xim luam ntawv muaj nuj nqi, kom tus neeg siv tuaj yeem tso tawm daim ntawv xeem.

 

Kev ntsuas thiab siv txoj kev

news-364-304

Txoj kev niaj zaus ntawm kev kuaj xyuas transformer yog raws li saum toj no. Huayi Fais fab transformer winding deformation tester yog tsim los ntawm lub ntsiab ntsuas thiab lub khoos phis tawj, thiab tseem muaj peb qhov tshwj xeeb ntsuas cables, ntsuas clip thiab grounding hlau. Lub ntsiab ntsuas qhov system thiab cov qauv ntsuas yog txuas nrog 50 lub siab zaus coaxial cable, cheb zaus teeb liab mus los ntawm qhov chaw nres nkoj tso zis (excitation output), thiab lub teeb liab clip (daj) txhaj cov teeb liab rau hauv cov khoom kuaj los ntawm kev txuas cable; lub teeb liab yog muab los ntawm cov khoom kuaj los ntawm cov teeb liab clip (ntsuab), thiab kis tau los ntawm cables (lus teb); lub teeb liab synchronous siv tau los ntawm cov khoom siv tshuaj ntsuam xyuas los ntawm kev ntsuas lub teeb liab, thiab xa mus rau cov tswv yim (siv cov tswv yim) ntawm cables. Cov ntaub thaiv npog ntawm cov ntaub ntawv kuaj thiab cov kab ntsuas yuav tsum tau txuas nrog kev ntseeg siab thiab hauv av. Cov xaim thiab roj tank ntawm cov transformer loj feem ntau yog txuas nrog hlau-core earthing bushing, raws li cov ntsiab lus hauv av, cov ntaub ntawv transformer yog grounded.

 

Kev txiav txim txoj cai

1. Waveform sib piv

Feem ntau kev khiav hauj lwm transformer windings yog zoo correlated nrog peb-theem yam ntxwv. Yog hais tias kev huam yuaj tsis ua rau winding deformation, cov nkhaus ua ntej thiab tom qab kev sib tsoo yeej coincide.

Tom qab lub winding yog deformed, lub nkhaus ua ntej thiab tom qab qhov kev huam yuaj pom tseeb deviate thiab tsis coincide, thiab correlation yog tsis zoo. Thaum lub sij hawm deformation, lub ncov tus nqi ntawm qhov nkhaus nyob rau hauv qis zaus band ntawm 0.5-200kHz yuav hloov, zaus ntxiv los yog txo. Tus naj npawb ntawm decibels sib raug rau tus nqi ncov kuj tseem yuav hloov, thiab tus naj npawb ntawm cov ntsiab lus ncov feem ntau yuav txo qis.

 

2. Kev txiav txim txoj kev xav

Piv nrog rau qhov zaus teb nkhaus ntawm transformer ua ntej kev huam yuaj, nws yuav tsum tau lub transformer kom muaj cov thawj zaus teb cov ntaub ntawv nkhaus.

Sib piv nrog cov khoom ntawm tib tus qauv thiab cov tuam ntxhab nyob rau tib lub sijhawm.

Phase-rau-theem sib piv yog ua tau rau peb-theem lossis ib-theem transformers.

Qhov kev txiav txim yog raws li ob tus yam ntxwv qhov tseem ceeb: txhais tau tias square yuam kev Exy thiab qhov sib txuas coefficient Pxy, qhov me dua qhov Exy yog, qhov ze dua qhov zoo dua rau ob txoj kab nkhaus. Qhov ze Pxy yog rau 1, qhov siab dua qhov zoo sib xws ntawm ob txoj kab nkhaus. Yog tias ob lossis ntau zaus bands muaj Pxy<0.98 and Exy>3. 0; sau Pxy<0.9 and Exy>1.5, or Exy>4.5 thiab Pxy tsuas yog 0.99, nws yuav ua rau deformation rau lub transformer. Ua ke nrog lwm txoj kev, xws li "roj chromatographic tsom xam", "winding DC kuj ntsuas" "luv-circuit impedance" "tsis muaj-load test" thiab lwm txoj kev los txiav txim siab seb lub transformer winding yog deformed.

HUAYI yog ib qho kev tshawb fawb thiab tsim kev lag luam rau cov khoom siv hluav taws xob hluav taws xob (kho, kuaj) kev tsim nyog thiab cov khoom siv hluav taws xob hauv Suav teb. Nws tshwj xeeb hauv kev kho cov khoom siv hluav taws xob kuaj nrog cov teeb tsa sib txawv uas xav tau qhov sib txawv voltages ..

HUAYI muaj kev txawj ntse hauv kev tshawb fawb thiab tsim cov khoom siv hluav taws xob ntsuas hluav taws xob thiab ntau yam cuab yeej! Nws muab kev pabcuam rau 24 teev: 400-060-1718. Xav paub ntau ntxiv txog Huayi, thov mus saib peb lub vev xaib: www.wh-huayi.com.

Xa kev nug