Kev paub

DGA cov txiaj ntsig tau txhais li cas - cov txheej txheem tseem ceeb yog dab tsi?

May 15, 2026 Tso lus

Kuv muaj daim ntawv tshaj tawm DGA nrog ntau ntawm xya gases. Kuv yuav hloov cov lej no li cas rau kev kuaj mob?

 

A: Peb qhov kev lees paub thoob ntiaj teb kev sib piv txoj kev hloov cov roj concentration rau hauv hom kev kuaj mob. Siv tag nrho peb rau kev hla - pov thawj.

Txoj Kev 1: IEC 60599 / IEEE C57.104 Duval Daim duab peb sab (feem ntau siv)

Zone

Hom txhaum

Hom Gas Kos Npe

PD

Kev tso tawm ib nrab

H₂ dominant, me CH₄

D1

Tsawg- tawm hluav taws xob (tws)

C₂H₂> 4% ntawm tag nrho HC

D2

Siab - zog tawm (arcing)

C₂H₂ + C₂H₄ dominant

T1

Thermal txhaum <300 degree

CH₄ + C₂H₆ tseem ceeb

T2

Thermal txhaum 300℃-700 degree

C₂H₄ > CH₄

T3

Thermal txhaum> 700 degree

C₂H₄ + H₂ siab

DT

Thermal + hluav taws xob (sib xyaw)

Cov qauv sib xyaw

Txoj Kev 2: IEEE C57.104 Gas Concentration Limits

Roj

Qhov xwm txheej 1 (Normal)

Xwm Txheej 2 (Ceev faj)

Yam 3 (Alert)

Hom 4 (High Risk)

H₂

Tsawg dua lossis sib npaug li 100 ppm

101-200 ppm

201-300 ppm

>300 ppm

CH ₄

Tsawg dua lossis sib npaug li 75 ppm

76-125 ppm

126-200 ppm

>200 ppm

C₂H₄

Tsawg dua lossis sib npaug li 100 ppm

101-200 ppm

201-300 ppm

>300 ppm

C₂H₂

Tsawg dua lossis sib npaug li 3 ppm

4-10 ppm

11-35 ppm

>35ppm ua

CO

Tsawg dua lossis sib npaug li 350 ppm

351-570 hli

571-900 hli

>9 00ppm

TDCG

Tsawg dua lossis sib npaug li 720 ppm

721–1,920 ppm

1,921–4,630 ppm

>4,630 pwm

Diagnostic workflow:

1. Sib piv txhua cov pa roj rau IEEE C57.104 Cov xwm txheej theem → ntsuas qhov ceev.

2. Xam Duval Daim duab peb sab ratios → txheeb xyuas hom txhaum.

3. Hla-xyuas nrog cov roj sib piv tseem ceeb (Rogers/Doernenburg).

4. Txheeb xyuas cov xwm txheej keeb kwm yav dhau los - yog qhov hloov pauv nrawm?

5. Yog hais tias tsis meej pem los yog tiam tus nqi> 30% / hli, txo sampling lub sij hawm.

Xa kev nug